Safety Gear Store are able to install, commission and service your fixed gas detection system. We offer a professional service from fully trained, certified and manufacturer approved engineers, we are also one of the only suppliers with engineers that carry spares in their vehicles to ensure a quick and efficient service that will enable you to continue using your facility.For more information on what we offer please visit one of the below pages:
Fixed Gas Detection System Install and Commissioning
Fixed Gas Detection System Calibration and Servicing
Operating Temperature:
Effect of Temperature
Zero
Sensitivty
0°C to +40°C (32°F to 104°F)
No effect (0°C to 20°C)
< ± 0.005ppm / °C (20°C to 40°C)
< ± 1.8% of measured value / °C
Operating Humidity (continuous):
Effect of Humidity
Sensitivity
20 – 75% rH
< 0.003ppm / % rH
< ± 0.3% of measured value / % rH
Long Term Drift
< ± 2ppm / year
< 10% of measured value / year
Midas Halogen Group (CI2 F2) Sensor Cartridge Spec Sheet